A variable frequency drive that worked correctly in one factory may need to be checked again after moving to a hotter workshop or a high altitude installation. Its nameplate rated output current has not changed, but its permitted continuous output current may be lower under the new conditions. This is why VFD derating matters to drive sizing, even when the motor power in kW or HP remains unchanged.
The practical question is not simply whether a VFD needs a larger power rating. It is whether the selected drive can deliver the required current continuously, meet the load's overload demands, and operate within the manufacturer's installation limits. This guide explains how to collect site data, read a VFD derating curve, calculate usable current, and decide whether to keep, cool, or replace a drive.
Quick Answer: Identify the exact VFD model and operating conditions, then obtain the applicable manufacturer rating and derating rule. Where one output current factor applies, calculate usable current = rated continuous current × derating factor. Compare the result with required motor current and check overload and installation limits separately.
Does Your VFD Actually Need Derating?
What VFD Derating Changes and What It Does Not
VFD derating means limiting a specified drive rating under particular operating conditions. Here, the main concern is available continuous output current, not a change to the motor's nameplate power.
|
Parameter |
Meaning |
|
Rated output current |
Continuous current specified for an identified drive and duty rating |
|
Usable continuous current |
Current permitted after applicable operating limits are considered |
|
Motor FLA |
Motor nameplate full load amperes, an important sizing reference |
|
Overload capacity |
Separate short duration current capability under manufacturer rules |
Passing the continuous current check does not establish adequate overload capacity.
Five Warning Signs That a Derating Check Is Needed
Check the exact manual when any of these conditions changes:
- Higher ambient temperature: The air surrounding the drive may exceed its permitted rating without derating.
- Higher installation altitude: Reduced air density may affect cooling or other electrical limits.
- Higher carrier frequency: A quieter switching setting may increase internal losses.
- Different enclosure or mounting: Cabinet ventilation, mounting direction, spacing, and accessories may change the applicable rating.
- Different input supply: Voltage, phase configuration, or grounding arrangements may require a different assessment.
If none applies, verify that the original rating conditions still match the site. For introductory motor and VFD selection, see SZCT's guide to choosing a variable frequency drive.
Collect the Right Operating Data Before You Calculate
Measure the Temperature Where the Drive Operates
Room temperature may differ from the drive's surroundings. For example, a 35°C workshop may contain a control cabinet at 45°C. This is illustrative, not a universal temperature difference.
Follow the manual's temperature definition and measure during demanding production. Consider nearby heat sources, blocked filters, sunlight, and cabinet ventilation.
Record Altitude, Enclosure Type, and Mounting Conditions
Record altitude, drive enclosure rating, cabinet arrangement, mounting orientation, spacing, and cooling accessories. An IP54 cabinet does not make an enclosed IP20 drive an IP54 drive, nor does it establish the same thermal conditions.
Confirm the Motor and Electrical Supply Data
Record motor nameplate voltage, frequency, power, and full load current. Include supply details, application, duty, and overload requirements. Never estimate motor current from kW alone.
|
Required input |
Illustrative entry |
Source |
|
Motor full load current |
24 A |
Motor nameplate |
|
Supply voltage and phase |
400 V, three phase |
Site electrical data |
|
Maximum drive ambient |
45°C |
Site measurement |
|
Installation altitude |
1,800 m |
Project records |
|
Existing VFD model |
Complete order number |
Drive label |
|
Application and duty |
Conveyor, duty to confirm |
Process specification |
|
Mounting and cooling |
Cabinet, accessories to confirm |
Installation inspection |
Illustrative entries only. Mark missing measurements to be confirmed.
Find the Correct Manufacturer Rating and Derating Curve
Match the Exact Model Number and Manual Revision
A series name such as Siemens SINAMICS G120 or PowerFlex 525 is insufficient. Variants differ in modules, frames, enclosures, and cooling arrangements.
Copy the complete catalog number, identify voltage and options, and locate the corresponding manufacturer technical document. Record its number, revision, date, and applicable pages. On modular drives, confirm the power module.
SZCT lists a SINAMICS G120 power module identified as 6SL3210-1PE23-8UL0. Use this product page for identification, not as a substitute for Siemens derating data.
Check Continuous Current and Overload Duty Separately
Drives may publish different continuous ratings for Normal Duty, Heavy Duty, or other duty classes. Select the rating appropriate to the load, rather than the largest current shown on a listing.
Review short term overload magnitude, duration, recovery conditions, and the demands of loaded starts or acceleration independently. A conveyor and a centrifugal fan with the same motor kW can require different overload capabilities.
Read the Applicable Derating Curve
Read a VFD derating curve in this order:
- Match the voltage class, enclosure, mounting, accessories, and duty category.
- Locate the applicable ambient temperature or altitude on the horizontal axis.
- Follow the correct curve to the percentage of rated current on the vertical axis.
- Convert that percentage to a decimal factor, such as 80% to 0.80.
- Check notes, absolute operating limits, and any additional restrictions.
For an actual manufacturer example, Rockwell PowerFlex 520 technical data, 520-TD001I-EN-E (September 2025), page 17, shows different curves for mounting and enclosure arrangements. Page 18 permits two alternative high altitude treatments above 1,000 m: lower maximum ambient temperature by 5°C per additional 1,000 m or reduce output current by 10% per additional 1,000 m, subject to voltage and grounding limits. These are PowerFlex 520 rules, not universal VFD percentages.
Select the Correct Derating Method for Your Conditions
High Ambient Temperature
For VFD temperature derating, identify the permitted temperature without derating. If the measured value is higher, apply the manufacturer's method and confirm the absolute operating limit. A reduced current cannot authorize operation beyond that limit.
High Installation Altitude
For altitude derating, check the permitted range, voltage and grounding restrictions, and required method. As the Rockwell example shows, ambient temperature limits and current reduction may be alternatives. Do not automatically stack them.
Higher Carrier or Switching Frequency
A higher carrier frequency can reduce noise while increasing drive losses. Check whether the selected setting reduces rated current. Consider motor insulation and cable requirements too.
Single-Phase Input and Special Supply Conditions
Use published ratings for dedicated single phase drives. A three phase input model may use single phase only if explicitly permitted. Verify input current, voltage, protection, and revised output ratings. No universal 50% factor makes an unsupported connection acceptable.
|
Condition |
Where to check |
Avoid assuming |
|
High temperature |
Installation tables and current curves |
One temperature threshold fits every drive |
|
High altitude |
Altitude limits, grounding notes, current curves |
Every model loses the same percentage |
|
Higher carrier frequency |
Switching frequency specifications |
Nameplate current is always unchanged |
|
Special input supply |
Approved input configurations |
Any three phase drive accepts single phase |
Once the manufacturer's method is clear, current calculation becomes straightforward.
Calculate the Usable VFD Output Current
Basic Formula for a Single Applicable Derating Factor
Use the following VFD derating calculation only when the manufacturer identifies one applicable output current factor for the selected drive and operating configuration:
I_usable = I_rated × k
Here, I_usable is permitted continuous output current in amperes, I_rated is the correct manufacturer rated continuous output current in amperes, and k is the applicable decimal derating factor.
For an illustrative 30 A drive with an assumed factor of 0.80:
30 A × 0.80 = 24 A usable continuous current
This is a mathematical example, not a verified factor for any particular model. For preliminary VFD sizing after derating, rearrange the formula:
I_rated,required ≥ I_required ÷ k
This reverse calculation identifies the minimum nominal continuous current to investigate. It does not establish a compatible order number or eliminate the need to check the candidate's own ratings.
How to Handle Multiple Derating Factors
Temperature and altitude can occur together, perhaps with a higher carrier frequency. Do not automatically multiply three independently found factors. Determine which of the following instructions the manufacturer actually provides.
Method A: Combined curve or table. Read the allowable current for the specified combination directly. Do not split the result into separate invented factors.
Method B: Explicit multiplication. Multiply only the factors the manufacturer instructs you to combine, using the stated conditions and calculation order.
Method C: Another method or unclear guidance. Follow prescribed alternate limits, use the relevant engineering selection procedure, or obtain manufacturer clarification. Do not substitute addition, multiplication, or an average.
A conservative looking calculation can still be technically incorrect if it ignores an absolute temperature, altitude, or insulation limit.
When a Formula Is Not Enough
A result above the required motor current is only a preliminary pass. Confirm supply compatibility, allowed ambient temperature, altitude, mounting, cooling accessories, and applicable duty class. Separately check overload capacity and motor protection. Calculated current is not the same as an approved operating condition.
Worked Example: Should You Keep or Replace Your Existing VFD?
Define the Motor, Drive, and Derating Assumptions
Consider this hypothetical engineering example, created to show how a current calculation affects the replacement decision. Neither drive represents a verified SZCT product specification.
|
Example input |
Value |
|
Required continuous motor current |
24 A |
|
Existing VFD continuous rating |
28 A |
|
Assumed applicable derating factor |
0.80 |
|
Candidate VFD continuous rating |
32 A |
For illustration, both drives use the same assumed factor. In practice, each complete model may have different ratings and derating rules. Overload, supply, cooling, and control compatibility remain unverified.
Calculate the Available Current
Existing drive: 28 A × 0.80 = 22.4 A
Candidate drive: 32 A × 0.80 = 25.6 A
|
Comparison |
Existing drive |
Candidate drive |
|
Nominal continuous current |
28 A |
32 A |
|
Usable current after assumed derating |
22.4 A |
25.6 A |
|
Required continuous current |
24 A |
24 A |
|
Preliminary current result |
Below requirement |
Above requirement |
Although 28 A exceeds 24 A on paper, derating leaves the existing drive 1.6 A short.
The candidate exceeds the requirement by 1.6 A. The reverse calculation gives 24 A ÷ 0.80 = 30 A as a preliminary minimum nominal rating under these assumptions.
Check What the Calculation Does Not Prove
This result does not verify starting overload, supply, protective devices, braking, cabinet space, or PLC communication. Confirm the candidate's real derating factor from its manual.
Decide Whether Upsizing Is Necessary
The 28 A drive fails this assumed current check; the 32 A candidate passes it. Evaluate cooling improvements before selecting a verified replacement. This is not approval of the candidate.
If your own calculation shows a current shortfall, send SZCT the existing drive model and operating conditions for a model sourcing enquiry.
Upsize, Improve Cooling, or Choose a Different Drive?
Improve the Installation Environment
If temperature is the main constraint, inspect blocked filters, failed fans, congested air paths, and nearby heat sources before replacing equipment. Correct the cooling arrangement within manufacturer requirements, then measure the drive's actual operating ambient again. SZCT's Siemens VFD thermal management guide provides a broader introduction to cooling and enclosure considerations.
Select a Drive with More Usable Current
If the verified derated current remains below the load requirement, compare candidates by usable continuous current, not simply their kW labels. Confirm each candidate's own duty rating, current curve, overload capacity, dimensions, and cooling needs. A larger drive may introduce installation changes that must be planned.
Choose a Drive Designed for the Actual Conditions
Where high altitude, dust, restricted ventilation, or unusual power supply is the main issue, another drive configuration may suit the site better than simply selecting a higher current rating.
|
Option |
Appropriate when |
Verify before approval |
|
Improve cooling |
Thermal conditions can be corrected |
New measurements and installation rules |
|
Increase current rating |
Verified usable output remains insufficient |
Duty, overload, protection, and fit |
|
Change drive configuration |
Existing series has site limitations |
Permitted environment and system compatibility |
Verify the Replacement VFD Before Ordering
Check the Manufacturer-Specific Requirements
SZCT supplies industrial automation products across several VFD brands. Its category pages are useful for exploring options, while final derating decisions must use the exact manufacturer's documentation.
|
Drive family |
Manufacturer data to verify |
SZCT category |
|
Siemens SINAMICS G120 |
Exact power module, duty class, altitude, temperature |
|
|
Allen-Bradley PowerFlex 525 |
Catalog number, mounting, enclosure, current curve |
|
|
ABB ACS series |
Model current rating, environmental limits, options |
|
|
Schneider Electric Altivar |
Duty rating, switching frequency, temperature limits |
For a broader comparison of automation ecosystems and drive families, see SZCT's VFD brand comparison guide.
Verify Electrical and Mechanical Compatibility
Two drives with similar usable current are not necessarily interchangeable. Check input supply, motor voltage and current, overload requirements, branch circuit protection, and any motor cable or output filter needs. Confirm physical dimensions, mounting holes, cabinet clearances, enclosure rating, cooling accessories, and heat dissipation.
Then check control mode, PLC communication protocol, analog and digital I/O, braking, feedback, and applicable safety functions. For replacements, preserve the original part number, connection records, and a parameter backup. Cross brand substitution often requires engineering changes rather than a direct component swap.
Confirm Protection Settings After Upsizing
Before commissioning, qualified personnel should verify motor rated current settings, thermal protection, overload limits, acceleration parameters, and coordination with the electrical installation. Do not assume a larger drive's default settings adequately protect the original motor. Follow the manufacturer's commissioning instructions and validate the installed system.
Explore the available variable frequency drive categories only after defining these requirements.
VFD Derating Worksheet: What to Send for Model Selection
Minimum Information for a Derating Review
A useful VFD selection request starts with the current equipment and operating conditions. Copy this worksheet into your enquiry:
|
Information |
What to provide |
|
Existing drive |
Brand and complete part number |
|
Motor |
Rated voltage, FLA, power, frequency |
|
Supply |
Voltage, phase count, frequency |
|
Environment |
Maximum drive ambient temperature, altitude |
|
Installation |
Enclosure, mounting, spacing, fan accessories |
|
Application |
Pump, fan, conveyor, or other load; overload duty |
|
Purchasing |
Quantity, destination, acceptable alternatives |
Nameplate and cabinet photos may resolve missing details.
Example of a Complete VFD Selection Request
We need to review a replacement VFD for a motor requiring 24 A continuous output current. Supply is 400 V, three phase. The drive is installed in a cabinet; maximum ambient temperature, altitude, and mounting details are attached. Existing VFD part number: [insert]. Application and required overload duty: [insert]. Quantity and delivery country: [insert]. Please advise available options, specifications requiring confirmation, and quotation terms.
Illustrative request only. Fill in the missing fields.
How SZCT Can Help with Model Sourcing
SZCT offers VFD product categories and an enquiry channel across several automation brands. Submit the complete part number and operating data, then ask for candidate specifications, availability, and quotation terms. Never assume a series name guarantees compatibility or stock.
Send your VFD specifications for a quote.
Conclusion: Calculate First, Verify the Model, Then Select
A reliable VFD selection begins with actual site conditions and manufacturer data, not a universal temperature or altitude percentage. Identify the correct duty rating, apply only the authorized derating method, and compare usable continuous output current with the application's requirement. Then verify overload performance, electrical supply, cooling, protection, and control compatibility.
If the existing drive passes all relevant checks, replacement may be unnecessary. If cooling improvements are practical, validate them before changing equipment. When a different unit is needed, use the SZCT VFD catalog and request a model and availability check with your worksheet.
FAQ

What is a VFD derating factor?
How do you calculate derated VFD output current?
At what temperature does a VFD need derating?
Does high altitude always require VFD derating?
How do you combine temperature and altitude derating?
Can a three-phase VFD run on single-phase input without derating?